Power Distribution
7.3.3.2 Installation options for 700 mm wide symmetrical racks
Performing the task
Ê Install two PDU brackets as described on page 69.
Figure 51: 32 A three-phase 15-way socket strip mounted in a 700 mm wide symmetrical rack
Rack height Installation direction vertically Installation direction horizontally
42 HU conditionally possible
1
Max. 2x with PDU kit 3 HU
24 HU
conditionally possible
1
1
Installation is only possible on the rear side. Cable routing is restricted. Installation of cable
arms at the same height is not possible.
Max. 2x with PDU kit 3 HU
Table 9: Installation options for asymmetrical racks